Transformer TypesΒΆ
The TransformerType components describe standard 2-winding transformer types.
If for a Transformer the attribute type is non-empty, the electrical
parameters of the TransformerType are mapped to the Transformer.
| attribute | type | unit | default | description | status |
|---|---|---|---|---|---|
| name | string | nan | nan | Unique name | Input (required) |
| f_nom | float | Hz | 50 | Nominal frequency | Input (required) |
| s_nom | float | MVA | 0 | Rated apparent power | Input (required) |
| v_nom_0 | float | kV | 0 | Nominal voltage on high voltage side | Input (required) |
| v_nom_1 | float | kV | 0 | Nominal voltage on low voltage side | Input (required) |
| vsc | float | Percent | 0 | Short circuit voltage | Input (required) |
| vscr | float | Percent | 0 | Real part of short circuit voltage | Input (required) |
| pfe | float | kW | 0 | No load (open circuit) iron losses | Input (required) |
| i0 | float | Percent | 0 | No load (open circuit) current | Input (required) |
| phase_shift | float | Degrees | 0 | Phase shift angle | Input (required) |
| tap_side | int | nan | 0 | Defines if tap changer is modelled at the primary 0 side (usually high-voltage) or the secondary 1 side (usually low voltage) (must be 0 or 1, defaults to 0) | Input (required) |
| tap_neutral | int | nan | 0 | Rated tap position, i.e. position at which the winding ratio corresponds to the ratio of the rated voltages | Input (required) |
| tap_min | int | nan | 0 | Minimum tap position | Input (required) |
| tap_max | int | nan | 0 | Maximum tap position | Input (required) |
| tap_step | float | Percent | 0 | Tap step size in percentage of voltage change | Input (required) |
| references | string | nan | nan | References for electrical parameters | Input (optional) |
The following standard transformer types are available, which are based on pandapower's standard types, whose parameterisation is in turn based on DIgSILENT PowerFactory.
| name | f_nom | s_nom | v_nom_0 | v_nom_1 | vsc | vscr | pfe | i0 | phase_shift | tap_side | tap_neutral | tap_min | tap_max | tap_step | references |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 0.25 MVA 10/0.4 kV | 50 | 0.25 | 10 | 0.4 | 4 | 1.2 | 0.6 | 0.24 | 150 | 0 | 0 | -2 | 2 | 2.5 | pandapower;Oswald - Transformatoren - Vorlesungsskript Elektrische Energieversorgung I;Werth Netzberechnung mit Erzeugungsprofilen |
| 0.25 MVA 20/0.4 kV | 50 | 0.25 | 20 | 0.4 | 6 | 1.44 | 0.8 | 0.32 | 150 | 0 | 0 | -2 | 2 | 2.5 | pandapowe;Oswald - Transformatoren - Vorlesungsskript Elektrische Energieversorgung I;Werth Netzberechnung mit Erzeugungsprofilenr |
| 0.4 MVA 10/0.4 kV | 50 | 0.4 | 10 | 0.4 | 4 | 1.325 | 0.95 | 0.2375 | 150 | 0 | 0 | -2 | 2 | 2.5 | pandapower;Oswald - Transformatoren - Vorlesungsskript Elektrische Energieversorgung I;Werth Netzberechnung mit Erzeugungsprofilen |
| 0.4 MVA 20/0.4 kV | 50 | 0.4 | 20 | 0.4 | 6 | 1.425 | 1.35 | 0.3375 | 150 | 0 | 0 | -2 | 2 | 2.5 | pandapower;Oswald - Transformatoren - Vorlesungsskript Elektrische Energieversorgung I;Werth Netzberechnung mit Erzeugungsprofilen |
| 0.63 MVA 10/0.4 kV | 50 | 0.63 | 10 | 0.4 | 4 | 1.0794 | 1.18 | 0.1873 | 150 | 0 | 0 | -2 | 2 | 2.5 | pandapower;Oswald - Transformatoren - Vorlesungsskript Elektrische Energieversorgung I;Werth Netzberechnung mit Erzeugungsprofilen |
| 0.63 MVA 20/0.4 kV | 50 | 0.63 | 20 | 0.4 | 6 | 1.206 | 1.65 | 0.2619 | 150 | 0 | 0 | -2 | 2 | 2.5 | pandapower;Oswald - Transformatoren - Vorlesungsskript Elektrische Energieversorgung I;Werth Netzberechnung mit Erzeugungsprofilen |
| 100 MVA 220/110 kV | 50 | 100 | 220 | 110 | 12 | 0.26 | 55 | 0.06 | 0 | 0 | 0 | -9 | 9 | 1.5 | pandapower;Oswald - Transformatoren - Vorlesungsskript Elektrische Energieversorgung I;Werth Netzberechnung mit Erzeugungsprofilen |
| 160 MVA 380/110 kV | 50 | 160 | 380 | 110 | 12.2 | 0.25 | 60 | 0.06 | 0 | 0 | 0 | -9 | 9 | 1.5 | pandapower;Oswald - Transformatoren - Vorlesungsskript Elektrische Energieversorgung I;Werth Netzberechnung mit Erzeugungsprofilen |
| 25 MVA 110/10 kV | 50 | 25 | 110 | 10 | 10.04 | 0.276 | 28.51 | 0.073 | 150 | 0 | 0 | -9 | 9 | 1.5 | pandapower;Oswald - Transformatoren - Vorlesungsskript Elektrische Energieversorgung I;Werth Netzberechnung mit Erzeugungsprofilen |
| 25 MVA 110/20 kV | 50 | 25 | 110 | 20 | 11.2 | 0.282 | 29 | 0.071 | 150 | 0 | 0 | -9 | 9 | 1.5 | pandapower;Oswald - Transformatoren - Vorlesungsskript Elektrische Energieversorgung I;Werth Netzberechnung mit Erzeugungsprofilen |
| 40 MVA 110/10 kV | 50 | 40 | 110 | 10 | 10.04 | 0.295 | 30.45 | 0.076 | 150 | 0 | 0 | -9 | 9 | 1.5 | pandapower;Oswald - Transformatoren - Vorlesungsskript Elektrische Energieversorgung I;Werth Netzberechnung mit Erzeugungsprofilen |
| 40 MVA 110/20 kV | 50 | 40 | 110 | 20 | 11.2 | 0.302 | 31 | 0.08 | 150 | 0 | 0 | -9 | 9 | 1.5 | pandapower;Oswald - Transformatoren - Vorlesungsskript Elektrische Energieversorgung I;Werth Netzberechnung mit Erzeugungsprofilen |
| 63 MVA 110/10 kV | 50 | 63 | 110 | 10 | 10.04 | 0.31 | 31.51 | 0.078 | 150 | 0 | 0 | -9 | 9 | 1.5 | pandapower;Oswald - Transformatoren - Vorlesungsskript Elektrische Energieversorgung I;Werth Netzberechnung mit Erzeugungsprofilen |
| 63 MVA 110/20 kV | 50 | 63 | 110 | 20 | 11.2 | 0.322 | 33 | 0.086 | 150 | 0 | 0 | -9 | 9 | 1.5 | pandapower;Oswald - Transformatoren - Vorlesungsskript Elektrische Energieversorgung I;Werth Netzberechnung mit Erzeugungsprofilen |